Fire Regulations

UK Fire Regulation Documents

In England and Wales, Scotland and Northern Ireland there are separate documents for domestic and non-domestic buildings.

There is much detail in the Fire safety documents that has little relevance to insulation materials. This section, therefore, concentrates on the requirements for:

  • Cavity barriers
  • Structural fire protection

 

Cavity barriers

Relevant sections:

  • Approved Document B (Domestic) B3 – Section 6: Concealed spaces (Cavities)
  • Approved Document B (Non-domestic) B3 – Section 9: Concealed spaces (Cavities)
  • Scottish Technical Handbook 2 – Fire Section 2.4: Cavities
  • NI Technical Booklet E – Section 3: Provision of cavity barriers

 

Fire and smoke spread in concealed spaces is particularly hazardous because fire can spread quickly whilst remaining undetected. The regulations give guidance on two types of cavity barrier:

  • Small cavity barriers that form a potential pathway around a fire-resisting wall or floor.
  • Extensive cavities, such as pitched roof spaces or suspended ceilings above offices.

 

Small cavity barriers

Cavity barriers should be provided to seal the edges of cavities, including around openings. In addition, where a compartment wall, floor or other part of a building abuts a structure containing a cavity, a cavity barrier should be installed so as to extend the line of the structure. There are a number of exceptions to this rule, the main one being a masonry cavity wall, which does not need cavity barriers at junctions with other fire-resisting constructions.

The Summary (Table 27) lists where cavity barriers are required by the Regulations. The table is taken from the Northern Ireland Technical Booklet E.

Small cavity barriers should provide at least 30 minutes fire resistance. Acceptable materials are:

  • steel at least 0.5mm thick
  • timber at least 38mm thick
  • polythene sleeved mineral wool, or mineral wool slab under compression
  • calcium silicate, cement or gypsum based boards at least 12mm thick

 

Table 27: Summary of small cavity barrier provision

Item

Cavity barriers to be provided

Purpose group to which the provision applies*

    1a 1b,1c 2 3,4,5,6,7
1

At the top of an external cavity wall and at the junction between anexternal cavity wall and a compartment wall that separates buildings,except for masonry external cavity walls

Y Y Y Y
2

Above the enclosures to a protected stairway in a dwellinghouse of three or more storeys

n/a Y n/a n/a
3

At the junction between an external cavity wall and every compartment floor and compartment wall, except for masonry external cavity walls

Y n/a Y Y
4

At the junction between a cavity wall and every compartment floor, compartment wall, or other wall or door assembly which forms a fire-resisting barrier, except for masonry external cavity walls

Y n/a Y Y
10

At the edges of cavities (including around openings)

Y Y Y Y

 

* Key to purpose groups in tables

1a

 Flat 3

Offices

1b

 Houses with three storeys 4

Retail and commercial

1c

 Houses up to two storeys 5

Assembly and recreation

2

Residential (institutional), eg hotel,

hospital wards, halls of residence

6

Industrial

    7

Storage

Large cavities

Cavity barriers should also be used to sub-divide larger cavities. The requirements for England and Wales, Northern Ireland and Scotland are shown in the tables below.

Table 28: Summary of large cavity barrier provision

Item

Cavity barriers to be provided

Purpose group to which the provision applies*

    1a 1b,1c 2 3,4,5,6,7
1

In a protected escape route, above and below any fire-resisting construction which is not carried full storey height or (in the case of a top storey) to the underside of the roof covering except for masonry external cavity walls

Y n/a Y Y
2

Above any bedroom partitions which are not carried full storey height, or (in the case of a top storey) to the underside of the roof covering

n/a n/a n/a n/a
3

Above any corridor enclosures which are not carried full storey height, or (in the case of a top storey) to the underside of the roof covering, where the corridor (which is not a protected corridor) is subdivided to prevent fire or smoke affecting two alternative escape routes simultaneously

n/a n/a Y Y
4

To subdivide any cavity (including any roof space) so that the distance between cavity barriers does not exceed the set dimensions (see tables below)

n/a n/a Y Y
5

Within the void behind the external face of rainscreen cladding at every floor level, and on the line of compartment walls abutting the external wall, of buildings which have a floor more than 18 m above ground level

Y n/a Y n/a
6

At the edges of cavities (including around openings)

Y Y Y

Y

 

Table 29: Maximum dimensions of cavities in non-domestic buildings (England, Wales and N.I.)†

Location of cavity Class of product/surface exposed in cavity Maximum dimension in any direction
  National class European class (m)
Between roof and a ceiling Any Any 20
Any other cavity Class 0 or Class 1 Class A1, or Class A2-s3, d2, or Class B-s3, d2, or Class 3-s3, d2 20
  Not Class 0 or Class 1 Not any of the above 10

Notes:

The National and European classes do not correspond exactly

† Purpose Groups 2-7

Table 30: Recommended distance between cavity barriers in roof spaces above undivided spaces (Scotland)
 

Where surfaces are non-combustible or low risk materials (m)

Where surfaces are medium, high or very high risk (m)

Intended for sleeping

20 15

Not intended for sleeping

No limit ‡

20

‡ Limit of 20 m should be applied in residential care buildings and hospitals.

Structural fire protection

Relevant sections:

  • Approved Document B (Domestic) B3 – Section 4: Loadbearing elements of structure
  • Approved Document B (Non-domestic) B3 – Section 7: Loadbearing elements of structure
  • Scottish Technical Handbook 2 – Fire Section 2.3: Structural protection
  • NI Technical Booklet E – Section 3: Fire resistance of elements of structure

Every building must be designed and constructed in such a way that in the event of an outbreak of fire, the load-bearing capacity of the building will be maintained to:

  • enable all occupants to escape
  • reduce the risk to firefighters
  • reduce the danger of collapse to people in the vicinity

The level of fire resistance required is between 15 and 120 minutes and depends on:

  • the use of the building
  • the height of the building both above and below ground
  • whether a sprinkler system is installed, or not

The important point to consider is the ability of the element of structure to maintain its load-bearing capacity in a fire for the period set out in the relevant table. The following tables list the level of fire resistance required for specific applications:

  • Approved Document B (Domestic) – Appendix A, Table A1
  • Approved Document B (Non-domestic) – Appendix A, Table A1
  • Scottish Technical Handbook 2 – Fire – Tables to clause 2.1.1 and Appendix 2D
  • NI Technical Booklet E – Table 3.2 Minimum periods of fire resistance

For Technical Advice Call 01744 76 66 66