Pc01-Between & Above Joists in One Layer
PC01 - Between and above joists one layer
Advantages
- Insulation installed in a single layer
- Lowest cost solution
- Familiar construction method
- Excellent thermal performance
- Enhances acoustic performance
|
 |
Products
Crown Loft Roll One is made from glass mineral wool and formed
into unfaced rolls which are lightweight, flexible, resilient and
noncombustible. Its manufacture has a very low impact on the
environment and is classified as Zero ODP and Zero GWP*
Optional
Knauf Breatheline is a breathable membrane and Type LR Roof Tile
Underlay with a polypropylene non-woven coating on both sides
* Ecohomes and Code for Sustainable Homes
classification
Typical construction
A pitched roof of timber trussed rafters with tiles or slates on
battens and Roof Tile Underlay optionally on sarking board.
Plasterboard ceiling below. Crown Loft Roll One is installed in one
layer between and overlapping the joists to minimise thermal
bridging through the ceiling joists
Ventilation requirements
If using Breatheline or similar third party accredited type LR
roof tile underlay with a well sealed ceiling – no ventilation
required In all other circumstances ventilation at eaves and ridge
required.
Installation
Crown Loft Roll One is laid between the joists. The insulation
should be taken over the wall plate to link up with the wall
insulation. All joints between the insulation to be close butted.
The insulation should be pushed up tight against the Roof Tile
Underlay if no ventilation is required or tight to the eaves
ventilator, taking care not to block the ventilation air path if
ventilation is required.
Performance
Thermal performance
Crown Loft Roll One has a thermal conductivity of 0.044 W/mK.
Table 1 gives U-values for typical constructions insulated with
Crown Loft Roll One.
Fire performance
Crown Loft Roll One is classified as Euroclass A1 to BS EN ISO
13501-1.
|
Typical specification
|
|
The whole area of the ceiling to be insulated with one layer
of Crown Loft Roll One of total thickness 270mm.
Width of insulation to be appropriate to the joist centres. The
insulation to be laid between the joists and to finish over wall
plate on external walls.
All joints between the rolls of insulation to be close
butted.
Maintain a minimum 25mm airspace between insulation and HR roof
tile underlay at the eaves.
Do not insulate under cold water tanks unless they are elevated.
Cold water tanks and pipes to be separately insulated.
Loft hatch to be insulated with a minimum 100mm depth of
insulation.
Alternatively, refer to NBS clauses: P10/120 and 130.
|
Typical section

Table 1: Typical U-values of ventilated
cold roof with ceiling level insulation
|
Product
|
Thickness (mm)
Between & Over Joists
|
U-values
(W/m2K)
|
| Crown Loft Roll One |
270 |
0.16 |
N.B. Joist sizes assumed to be 100 x 48mm at 600mm centres
(8% bridging plus 1% for cross noggings). The U-value has been
calculated in accordance with BS EN ISO 6946:1997.