UK Fire Regulation Documents

In England and Wales, Scotland and Northern Ireland there are separate documents for domestic and non-domestic buildings.

There is much detail in the Fire safety documents that has little relevance to insulation materials. This section, therefore, concentrates on the requirements for:

  • Cavity barriers
  • Structural fire protection

 

Cavity barriers

Relevant sections:

  • Approved Document B (Domestic) B3 – Section 6: Concealed spaces (Cavities)
  • Approved Document B (Non-domestic) B3 – Section 9: Concealed spaces (Cavities)
  • Scottish Technical Handbook 2 – Fire Section 2.4: Cavities
  • NI Technical Booklet E – Section 3: Provision of cavity barriers

 

Fire and smoke spread in concealed spaces is particularly hazardous because fire can spread quickly whilst remaining undetected. The regulations give guidance on two types of cavity barrier:

  • Small cavity barriers that form a potential pathway around a fire-resisting wall or floor.
  • Extensive cavities, such as pitched roof spaces or suspended ceilings above offices.

 

Small cavity barriers

Cavity barriers should be provided to seal the edges of cavities, including around openings. In addition, where a compartment wall, floor or other part of a building abuts a structure containing a cavity, a cavity barrier should be installed so as to extend the line of the structure. There are a number of exceptions to this rule, the main one being a masonry cavity wall, which does not need cavity barriers at junctions with other fire-resisting constructions.

The Summary (Table 28) lists where cavity barriers are required by the Regulations. The table is taken from the Northern Ireland Technical Booklet E.

Small cavity barriers should provide at least 30 minutes fire resistance. Acceptable materials are:

  • steel at least 0.5mm thick
  • timber at least 38mm thick
  • polythene sleeved mineral wool, or mineral wool slab under compression
  • calcium silicate, cement or gypsum based boards at least 12mm thick

 

Table 28: Summary of small cavity barrier provision

Item

Cavity barriers to be provided

Purpose group to which the provision applies*

    1a 1b,1c 2 3,4,5,6,7
1

At the top of an external cavity wall and at the junction between anexternal cavity wall and a compartment wall that separates buildings,except for masonry external cavity walls

Y Y Y Y
2

Above the enclosures to a protected stairway in a dwellinghouse of three or more storeys

n/a Y n/a n/a
3

At the junction between an external cavity wall and every compartment floor and compartment wall, except for masonry external cavity walls

Y n/a Y Y
4

At the junction between a cavity wall and every compartment floor, compartment wall, or other wall or door assembly which forms a fire-resisting barrier, except for masonry external cavity walls

Y n/a Y Y
10

At the edges of cavities (including around openings)

Y Y Y Y

 

* Key to purpose groups in tables

1a

 Flat 3

Offices

1b

 Houses with three storeys 4

Retail and commercial

1c

 Houses up to two storeys 5

Assembly and recreation

2

Residential (institutional), eg hotel,

hospital wards, halls of residence

6

Industrial

    7

Storage

Large cavities

Cavity barriers should also be used to sub-divide larger cavities. The requirements for England and Wales, Northern Ireland and Scotland are shown in the tables below.

Table 29: Summary of large cavity barrier provision

Item

Cavity barriers to be provided

Purpose group to which the provision applies*

    1a 1b,1c 2 3,4,5,6,7
1

In a protected escape route, above and below any fire-resisting construction which is not carried full storey height or (in the case of a top storey) to the underside of the roof covering except for masonry external cavity walls

Y n/a Y Y
2

Above any bedroom partitions which are not carried full storey height, or (in the case of a top storey) to the underside of the roof covering

n/a n/a n/a n/a
3

Above any corridor enclosures which are not carried full storey height, or (in the case of a top storey) to the underside of the roof covering, where the corridor (which is not a protected corridor) is subdivided to prevent fire or smoke affecting two alternative escape routes simultaneously

n/a n/a Y Y
4

To subdivide any cavity (including any roof space) so that the distance between cavity barriers does not exceed the set dimensions (see tables below)

n/a n/a Y Y
5

Within the void behind the external face of rainscreen cladding at every floor level, and on the line of compartment walls abutting the external wall, of buildings which have a floor more than 18 m above ground level

Y n/a Y n/a
6

At the edges of cavities (including around openings)

Y Y Y

Y

 

Table 30: Maximum dimensions of cavities in non-domestic buildings (England, Wales and N.I.)†

Location of cavity Class of product/surface exposed in cavity Maximum dimension in any direction
  National class European class (m)
Between roof and a ceiling Any Any 20
Any other cavity Class 0 or Class 1 Class A1, or Class A2-s3, d2, or Class B-s3, d2, or Class 3-s3, d2 20
  Not Class 0 or Class 1 Not any of the above 10

Notes:

The National and European classes do not correspond exactly

† Purpose Groups 2-7

Table 31: Recommended distance between cavity barriers in roof spaces above undivided spaces (Scotland)
 

Where surfaces are non-combustible or low risk materials (m)

Where surfaces are medium, high or very high risk (m)

Intended for sleeping

20 15

Not intended for sleeping

No limit ‡

20

‡ Limit of 20 m should be applied in residential care buildings and hospitals.

Structural fire protection

Relevant sections:

  • Approved Document B (Domestic) B3 – Section 4: Loadbearing elements of structure
  • Approved Document B (Non-domestic) B3 – Section 7: Loadbearing elements of structure
  • Scottish Technical Handbook 2 – Fire Section 2.3: Structural protection
  • NI Technical Booklet E – Section 3: Fire resistance of elements of structure

Every building must be designed and constructed in such a way that in the event of an outbreak of fire, the load-bearing capacity of the building will be maintained to:

  • enable all occupants to escape
  • reduce the risk to firefighters
  • reduce the danger of collapse to people in the vicinity

The level of fire resistance required is between 15 and 120 minutes and depends on:

  • the use of the building
  • the height of the building both above and below ground
  • whether a sprinkler system is installed, or not

The important point to consider is the ability of the element of structure to maintain its load-bearing capacity in a fire for the period set out in the relevant table. The following tables list the level of fire resistance required for specific applications:

  • Approved Document B (Domestic) – Appendix A, Table A1
  • Approved Document B (Non-domestic) – Appendix A, Table A1
  • Scottish Technical Handbook 2 – Fire – Tables to clause 2.1.1 and Appendix 2D
  • NI Technical Booklet E – Table 3.2 Minimum periods of fire resistance

Residential refurbishmentResidential refurbishment

Fire precautions mainly come into play when a property is being converted into flats, or a dwelling is being extended by means of a loft conversion. The main consideration with conversion to flats is ensuring a safe means of escape.

Loft conversions are a very popular way of extending houses and bungalows. However, the implications for complying with the Fire requirements of the Building Regulations are complex. We set out the main considerations in this section. This guidance offers advice on loft conversions to existing bungalows and two storey dwellings – if you already have a three storey house and wish to convert the loft, you are advised to speak to your local Building Control department.

From 6th April 2007, the revised Approved Document B came into force, introducing significant changes to the fire requirements for loft conversions. Most of the previous concessions relating to loft conversions have now been removed. Existing two storey houses with a new loft conversion are to be treated as new three storey houses.

Loft conversionsLoft conversions

Form a protected escape route.

The revised Regulations require a fire resistant protected escape route from the loft to the dwelling’s final exit. This is to enable the occupants to make a safe escape. The protected escape route should either:

  • discharge into a hall served by an external door, or
  • there must be at least two separate escape routes available to an external door – separated by fire resistant construction and fire doors.

The protected escape route should be enclosed by construction (doors and walls or partitions) capable of resisting fire for at least 30 minutes. Existing walls should be assessed for their fire resistance and upgraded as necessary.

Penetrations of the fire resisting construction should be suitably fire stopped or fire protected eg tops of walls / around services / drainage pipes /air vents etc

If fire doors are not to be fitted to the bathroom (due to low fire risk – unless boilers are fitted) - then the fire protection needs to be checked around the perimeter of the bathroom walls as an extension of the escape route fire-protection.

The condition of existing doors and frames opening onto the protected stair must be assessed. If they do not provide at least 20 minutes fire resistance, they must be replaced with doors capable of achieving at least 20 minutes fire resistance.

Any glazing openings facing the protected escape route, other than those serving toilets or bathrooms, should be at least 1.1m above the floor level or stair pitch line and changed to achieve 30 minutes fire-resistance.

If escape windows are to be provided, they must have a clear opening of sufficient size to escape through and be located in a position amenable to rescue by ladder. For most properties, the escape windows must be provided on the front elevation.

Staircases

If the dwelling has an open plan staircase, it will need to be enclosed. The new loft access stair must be an extension of the existing stair enclosure to avoid the creation of inner rooms. Alternatively if there is only one room in the loft space, the loft stair can be contained within the room itself and a fire door provided at the base of stair landing position, where it exits onto the existing first floor landing. This guidance assumes the existing dwelling has at least two stories. The means of escape and fire protection required where a bungalow is to have a loft conversion are less onerous.

Fire resistant floors

For loft conversions to existing two storey dwellings, the new floor must have 30-minute fire-resistance ie 30 minutes load bearing capacity, 30 minutes integrity and 30 minutes insulation (30/30/30). If the existing ceilings are retained, they may need to be upgraded to achieve this rating. This can be done from above – see page 108.

If the building has a basement its ceiling should achieve at least 30 minutes fire resistance and the basement is to be separated from the ground floor by fire resisting construction.

Smoke detectors

Mains powered and battery backed up smoke detectors must be installed on each storey in accordance with BS 5839-6: 2004 – Grade D – category LD3 standard. All detectors must be interlinked so that they all sound even if only one is triggered. They must be placed in the circulation spaces or protected stairway. If the new loft has no circulation space, a smoke detector should be fitted in the loft room itself.

Position detectors so that they can be reached easily for maintenance and testing ie not over stairs.

Dormer windows

If the conversion involves forming a dormer, dormer cheeks within 1 metre of a boundary should achieve at least 30 minutes fire resistance in both directions. The dormer roof should also be capable of resisting external fire spread for at least 30 minutes.

Conversion to flatsConversion to flats

Where an existing house or other building is converted into flats, this counts as a material change of use under the Building Regulations and Approved Document B should be followed.

Approved Document B, Volume 2 – Buildings other than dwellings sets out comprehensive requirements for providing adequate means of escape for flats.

For buildings up to three storeys high where the means of escape is in accordance with Approved Document B, a 30 minute standard of fire resistance could be accepted for the elements of structure, including any timber separating floors. Where it is desirable to retain an existing ceiling, it is possible to upgrade a timber floor by inserting insulation from above. Doors to individual flats must have a 30 minute fire resistance. It is usual to design a protected entrance hall to each flat. The diagram shows a typical arrangement for a flat conversion.

For buildings with four or more storeys, at least 60 minutes fire resistance is required. Floors above basements also require at least 60 minutes fire resistance. This may be difficult to achieve with existing timber floors.

Website Options

Links To Other Country Sites
Mobile View

Latest News

Follow @KnaufUK on Twitter!

International