Non-residential acoustic
regulations
Hospital design
The Health Technical Memorandum (HTM) set out
the performance criteria for hospitals.The most relevant for
partitions are:
- HTM 56: Partitions
- HTM 57: Internal glazing
- HTM 58: Internal doorsets
- HTM 81: Fire precautions in new
hospitals
- HTM 2045: Acoustics – This HTM will
eventually replace the acoustic requirements in HTM 56.
In practice, the Building Regulations and
Health Technical Memorandums should be referred to as the
definitive guidance.
Acoustic performance
HTM 56 offers guidance on the design and
specification of partitions that will meet the general requirements
of users and conditions of use in health buildings.
Table 25 covers most of the common activity
spaces within a typical hospital. The table grades non-loadbearing
partitions according to their ability to provide minimum levels of
airborne sound insulation for certain areas of activity. For these,
and other areas, a number of possible solutions are available,
subject to project requirements.
Some key considerations to maintain sound
insulation performance are:
- Adequate sealing of the perimeter frame and
plasterboard faces and around penetrations
- The performance characteristics of
doors/internal glazing in comparison to that of the partition
(section 2.10 HTM 57). A well-fitting door of solid core
construction for instance, will achieve a sound insulation of 15-20
dB (section 2.10 HTM 58)
- Fitting of sound attenuators within ducts at
the point where the partition is penetrated
HTM 2045 ‘Design considerations’ is concerned
with the control, reduction and absorption of noise (and vibration)
in hospitals, excepting audiology facilities.
The general principles of HTM 2045 ‘Design
Considerations’ are that:
- Interior environments must be protected from
external noise sources
- Noise from interior areas should not
adversely intrude on other interior areas
- Internally generated noise should not
adversely affect the external environment
Table 25: Airborne sound insulation requirements
(HTM 56)
| Location |
1 |
2 |
2 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
| 1.Consulting rooms |
43 |
43 |
* |
48 |
43 |
48 |
43 |
53 |
53 |
* |
48 |
* |
48 |
* |
| 2.Examination rooms |
43 |
43 |
53 |
48 |
43 |
43 |
43 |
53 |
53 |
* |
48 |
* |
48 |
* |
| 3.Treatment rooms |
* |
53 |
43 |
* |
53 |
48 |
* |
48 |
43 |
43 |
48 |
43 |
48 |
* |
| 4.Speech therapy rooms |
48 |
48 |
* |
48 |
48 |
53 |
48 |
* |
* |
* |
53 |
* |
53 |
* |
| 5.Offices |
43 |
43 |
53 |
48 |
48 |
43 |
43 |
48 |
48 |
53 |
43 |
53 |
43 |
* |
| 6.Seminar rooms |
48 |
43 |
48 |
53 |
43 |
38 |
48 |
43 |
43 |
48 |
43 |
48 |
38 |
* |
| 7.Single-bed wards |
43 |
43 |
* |
48 |
43 |
48 |
43 |
53 |
53 |
* |
48 |
* |
48 |
* |
| 8.Multi-bed wards |
53 |
53 |
48 |
* |
48 |
43 |
53 |
43 |
43 |
48 |
48 |
48 |
43 |
* |
| 9.Day rooms |
53 |
53 |
43 |
* |
48 |
43 |
53 |
43 |
48 |
43 |
48 |
43 |
48 |
* |
| 10.Nurseries |
* |
* |
43 |
* |
53 |
48 |
* |
48 |
43 |
43 |
48 |
43 |
48 |
* |
| 11.Toilets and bathrooms |
48 |
48 |
48 |
53 |
43 |
43 |
48 |
48 |
48 |
48 |
43 |
48 |
43 |
* |
| 12.Utility rooms |
* |
* |
43 |
* |
53 |
48 |
* |
48 |
43 |
43 |
48 |
43 |
48 |
* |
| 13.Ward pantries |
48 |
48 |
48 |
53 |
43 |
38 |
48 |
43 |
43 |
48 |
43 |
48 |
38 |
* |
| 14.Plant motor rooms |
* |
* |
* |
* |
* |
* |
* |
* |
* |
* |
* |
* |
* |
* |
|
1. Partitions between adjacent spaces marked * in this table
should, if possible, be designed out (ie do not locate these spaces
next to one another), because the satisfactory sound insulation of
partitions between them may require special construction.
2. In the case of plant rooms, there is no specified
requirement, and each situation needs separate consideration by the
designer.
3. The minimum airborne weighted sound reduction index
requirements are taken from BS 5821: Parts 2 & 3.
|
Fire considerations
HTM 56 provides a list of notes to assist the
building designer in meeting the fire precaution requirements of
the Building Regulations and the Firecode HTM 81: Fire precautions
in new hospitals. It also includes paragraphs on cavity barriers,
smoke control and surface spread of flame.
The main purpose of Firecode HTM 81 is to
provide guidance on the standards of fire safety expected in new
NHS hospitals. As fire safety is dependent not only on the physical
fire precautions provided, HTM 81 also considers the fire safety
implications of:
- The dependency of the patient
- Fire hazards within the hospital
- Management policies
- Availability of sufficient and adequately
trained staff
Where the guidance given in Firecode HTM 81 is
followed, The Building Regulations Part B will be satisfied.
Robustness of partitions
Appendix B of HTM 56 sets out performance
requirements for strength and stability of partitions. The tests
and levels of acceptance are taken from BS 5234: Part 2.
Partitions should be capable of meeting the
requirements of BS 5234: Part 1:1992 within the appropriate duty
category. The categories applicable to hospitals are:
- Medium duty (office)
- Heavy duty (public circulation and industrial
areas)
- Severe duty (major circulation and
heavy industrial areas)