Detailed Design Considerations
Building Regulations
Typical U-values for new build external walls are shown
below:
| |
U-value
(W/m2K) |
|
| England, Wales & NI |
0.27 |
|
| Scotland |
0.25 |
|
| Ireland |
0.27 |
|
Thermal Bridging at Junctions and
Openings
With improving U-values for walls and other elements, it has become
necessary to ensure that no cold bridges exist at junctions and
openings. In England and Wales Accredited Details have been
issued for housing, and these can be used to demonstrate Building
Regulations compliance in non-residential buildings of similar
construction. If these details are not suitable, the designer may
use other approved details or calculate heat loss through the cold
bridges.
The opposite page demonstrates suitable ways to avoid cold bridging
at junctions and openings. Polyfoam System Closer exceeds the
performance required for closing reveals and is suitable for
cavities up to 100mm wide.
Wall Ties
Apart from structural considerations, which are obviously
pre-eminent, the correct specification of wall ties is crucial in
two additional respects. Firstly, it is necessary that the tie does
not compromise performance of the cavity wall insulation with
regard to liquid water penetration.
Secondly, that the U-value calculation method takes into
consideration the number of wall ties per square metre as well as
the cross sectional area and thermal performance of the tie. Where
cavities are 100mm or less, stainless steel wire ties are
recommended as they have negligible effect on the wall U-value.
Where the cavity is over 100mm wide, a more robust tie is required,
which can have a significant effect on the wall U-value.
Masonry cavity walls and fire
performance
Open cavities must be stopped to prevent the passage of fire. This
is required at specific intervals and the cavity stop has to
provide at least 30 minutes fire resistance. If the cavity is fully
or partially filled and is built in accordance with Diagram 34
of Approved Document B, fire barriers are not required.
Prevention of liquid water
penetration
Prevention of liquid water penetration from the outer to inner leaf
is one of the major considerations when designing cavity walls. The
selection of appropriate materials and pointing methods for the
outer leaf are crucial.
Cavity trays
Cavity trays should be provided:
- at all interruptions of the cavity, such as lintels and sleeved
vents and ducts
- above insulation that stops short of the top of the wall
Cavity trays should rise at least 140mm within the cavity, be
self-supporting or fully supported with joints lapped and sealed.
Stop ends should be provided to the ends of all cavity trays.
Weepholes should be provided at not more than 900mm centres to
drain each cavity tray, with at least two weepholes per cavity
tray.
Condensation risk
In cavity wall construction it is necessary to ensure that there is
no danger of condensation forming within the inner leaf.
Condensation may have a detrimental effect on the thermal
performance of a structure or cause damp on the inside. Unfaced
mineral wool products, being ‘vapour open’ offer virtually no
resistance to the passage of water vapour and consequently will not
suffer from interstitial condensation.
The Knauf Insulation Academy Technical Advisory Centre are able to
carry out condensation risk calculations if further reassurance is
required.
Typical Robust Details
Three methods for insulating masonry cavity walls

The recommended masonry
cavity wall system is full fill, either 2) injected (Supafil) or 3)
built in slabs using Crown DriTherm Cavity Slab
These recommended systems not only provide the best U-value for a
given cavity wall thickness but are also the lowest in cost. Even
with dense concrete blocks it is possible to achieve very high
thermal performance in a manageable wall width. The systems shown
require no cavity barriers and have British Board of
Agrément Certificate approval to the same height as partial
fill systems.
With formal guarantees against liquid water penetration, and a long
history of use in wall construction, both Crown Supafil and Crown
DriTherm offer total peace of mind for the specifier, builder and
client alike. If a partial fill solution is adopted in order to
retain a residual cavity, the recommended system is Polyfoam
Cavityboard. The robust nature of Polyfoam Cavityboard allows the
formation of a shiplap detail on all edges of the board, offering a
further guarantee against water penetration and cold bridging that
might occur with plain square edge cellular plastic boards.
Typical Specification Clauses
1) Partial fill: Crown DriTherm Cavity
Slab
Crown DriTherm Cavity Slab ......mm thick to be located in the
cavity of all external masonry cavity walls.
The residual cavity width to be 25mm/ 50mm. Insulation to be
retained against the cavity face of the inner leaf of masonry by
means of insulation retaining wall ties as manufactured by ..... .
The wall ties to have one of their drip centres half-way across the
residual cavity.
The first run of wall ties to be located at 600mm centres
horizontally (at a level to be decided by the specifier). Ties
thereafter to be at 450mm centres vertically and a maximum of 600mm
horizontally.
All work under construction must be protected overnight and during
adverse weather conditions in accordance with BS 5628: Part 3:
1985.
Alternatively, refer to NBS clause: F30/12,151
2) Partial fill: Polyfoam
Cavityboard
Polyfoam Cavityboard, ......mm thick, to be located in the cavity
of all external masonry cavity walls; residual cavity width to be
....mm. Insulation to be retained against the cavity face of the
inner leaf of masonry by means of insulation retaining wall ties as
manufactured by ....... .
The wall ties to have one of their drip centres half-way across the
residual cavity.
The residual cavity width to be 25mm/50mm.
The first run of wall ties to be located at the bottom level of the
insulation (to be decided by the specifier). Ties to be at 450mm
centres vertically and a maximum of 900mm horizontally.
All work under construction must be protected overnight and during
adverse weather conditions in accordance with BS 5628: Part 3:
1985.
All work to be in strict accordance with this specification and the
recommendations contained in Knauf Insulation’s literature.
Alternatively, refer to NBS clause: F30/12,151
3) Crown Supafil
Crown Supafil Cavity Wall Insulation glass mineral wool to be
injected into the cavity by an Knauf Insulation/BBA Approved
Installer.
New cavity walls to receive Crown Supafil Cavity Wall Insulation by
injecting insulation into the cavity should be constructed so that
insulation cannot penetrate ventilation ducts or pass through to
cavities in adjoining buildings or compartments which are not to be
insulated. Close fitting ducts or sleeves should be installed
across the cavity to serve air bricks and other ventilation
openings. Cavity barriers should be installed at junctions with
other properties and compartments, and as required by the Building
Regulations.
Existing cavity walls to be inspected by the Approved Installer and
all necessary builder’s work carried out prior to Crown Supafil
Cavity Wall Insulation being injected.
All work to be in strict accordance with the procedures laid out in
the relevant BBA Certificate and the Knauf Insulation “Operators”
and “Survey & Assessment” manuals.
Alternatively, refer to NBS clause: P11/40,220
4) Full fill: Crown DriTherm Cavity
Slab
All external walls to be insulated during construction by
completely filling the cavities with Crown DriTherm Cavity
Slab
The first run of wall ties to be located at 600mm centres
horizontally (at a level to be decided by the specifier).
Subsequent runs of wall ties to be at not more than 900mm centres
horizontally, or as otherwise required by the structure, and at
450mm vertically.
All work under construction must be protected overnight and during
adverse weather conditions in accordance with BS 5628: Part 3:
1985.
Alternatively, refer to NBS clause: F30/10,150
5) Polyfoam System Closer
Install Polyfoam System Closers, 25mm thick ….mm wide (to equal
cavity width) at jambs and sills of all openings in masonry cavity
walls. Secure with the proprietary ties at maximum 500mm centres.
Ensure that closers fit tightly to each other and to the lintel.
The closer at the jamb must completely lap the closer at the
sill.
Alternatively, refer to NBS clause: F30/18,180
6) Polyfoam Combi Closer
Install Polyfoam Combi Closers, 25mm thick ….mm wide (to be cut,
where necessary, to equal cavity width) at jambs and sills of all
openings in masonry cavity walls. Secure with the proprietary ties
at maximum 500mm centres. Ensure that closers fit tightly to each
other and to the lintel. The closer at the jamb must completely lap
the closer at the sill.
Alternatively, refer to NBS clause: F30/18,180
7) Polyfoam Linerboard
Polyfoam Linerboard of insulation thickness .....mm with integral
9.5mm plasterboard to be fixed directly to inner masonry leaf by
adhesive*/ plaster dabs*/ mechanical fixing* (*delete as required)
using the method and materials recommended in Knauf insulation
literature.
When the adhesive has set, secure with two .....
(manufacturer/reference) mechanical fixings along the top edge of
each board (for adhesive/plaster dabs).
Alternatively, refer to NBS clause: K10/175,185,205